Part Number Hot Search : 
2SC1755E 2N2763 MSQ12002 KTC8550 MD3251 TC4424 RN4986 ZSWFXXX
Product Description
Full Text Search
 

To Download ANX-SR Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 specifications are for information only, are not intended for installation purposes, a nd are subject to change without notice. no responsibility is assumed by gamewell-fci for their use. ?2014 by honeywell international inc. all rights reserved. www.gamewell-fci.com 9020-0613 rev. m page 1 of 5 e3 series ? broadband system intelligent, networked, multi- channel fire alarm control and emergency voice evacuation system approved class 1 class 2 high rise city of chicago approved city of denver approved 7165-1703:125 fdny #: 6175 coa # 231-06-e mea approved 3025415 fm signaling s1869 description the gamewell-fci, e3 series ? broadband system includes the netsolo ? broadband system. like the net- solo broadband system, the e3 series broadband is of modular design and allows a wide range of configurations from two basic sub-assemblies. these sub-assemblies form an integrated, distribu ted fire alarm system that includes audio evacuation and fire command capability. the network communication transmits all fire alarm, audio evacuation, voice paging, and fire fighter communications. this system can be used as a component of the following e3 series systems: ? e3 series broadband voice evacuation system ? e3 series combined fire and mass notification system the e3 series broadband is a revolutionary advance in fire detection and emergency voice evacuation system design. e3 series broadband employs proven technology and expands it to accomplish emergency multi-channel voice evacuation, two-way fire fighter communications, and building control applications, all over a single pair of wires or fiber-optic cable. it is a true peer-to-peer, to ken ring passing, networked sys- tem capable of supporting up to 64 individual nodes. in addition, the addressable node expander (anx) board expands the network to 122 nodes. all system status, con- trol-by-event sequences, audio voice paging, and fire fighter telephone signals are sent between nodes over a single pair of wires or fiber-optic cable. each e3 series broadband node can be spaced along the network a maximum distance of 3,000 feet (914.4 m) over an unshielded, twisted-pair of wires or fiber-optic cable with up to 8db loss. built-in isolation at each node permits style 4, 6, and 7 network configurations. the e3 series broadband is simple to configure for any project requirement. a complete e3 series broadband application can be assembled from the following types of nodes; the ili-e3/ili95-e3 series, anx, the incc com- mand center, and the inx transponder. the e3 series broadband system is capable of the most sophisticated sequences of operations. e3 series ? and netsolo ? are registered trademarks of honeywell international inc. ul ? is a registered trademark of underwriters laboratories inc features ? ibc seismic certified. ? listed under ul ? standard 864, 9th edition. ? listed under ul standard ul2572 for mass notification. ? ul listed for smoke control (dedicated and non-dedicated) when properly configured. ? fm/ul listed for pre-action/deluge use. ? all communication signals and control-by-event sequences over a single pair of twisted, unshielded wires or fiber-optic cable. ? distributed architecture, including style 7 wiring configurations, allow system components to continue normal operation with no loss of function during single line fault conditions. ? integrates inx transponders and incc command cen- ters to create a complete audio evacuation system with up to 122 nodes. ? redundant command centers with microphone and fire fighter?s handset are easily configured by adding incc s. ? uses state-of-the-art digital signal processor (dsp) technology for efficient audio compression and filtering. ? provides up to 150 watts of audio power from 3 am-50 series amplifiers with an additional 50 watts of standby power in each intelligent network transponder (inx). e3 series broadband
gamewell-fci 12 clintonville road, northford, ct 06472-1610 us a ? tel: (203) 484-7161 ? fax: (203) 484-7118 9020-0613 rev. m page 2 of 5 www.gamewell-fci.com description (continued) the field configuration program (fcp) is based on bool- ean logic statements providing and, or, not, and xor logic operators. these operators can be combined to pro- duce additional boolean operators such as nand, nor, xnor. the e3 series broadband is software-programma- ble for multi-channel digital audio applications. it is ideal for use with a wide range of complex system applications including high-rise or campus installations. an array of cabinets allows for neat, compact, installations. a comprehensive set of timing functions can be attached to any input/output logic stat ement for the staggered reset of fan control relays, time-delayed alarm activation, auto- matic. the e3 is a microprocessor-based fire alarm control panel that uses an ili-e3/ili 95-e3 series, intelligent loop module or the anx with two signaling line circuits and two notification appliance circuits. when the e3 series trans- mits to remote locations, the optional rpt-e3 provides the ili-e3/ili95-e3 series or t he anx with signal boosting and transient protection, as well as connectivity for both wire and fiber-optic cables. options also include an integral digital alarm communicator tr ansmitter (dact) support- ing most popular reporting formats. incc (intelligent netw ork command center) the intelligent network comm and center (incc) serves as the point of interface between an operator and the sys- tem?s audio evacuation, fire fighter intercom, and building network. the incc occupies a single address on the e3 series broadband network. a typical incc assembly con- sists of the following: ? intelligent network interfac e-voice gateway (ini-vgc- fo or ini-vgc-utp) module (fiber-optic or unshielded twisted-pair). ? ini-vgc-utp (unshielded twisted-pair only). ? one or more addressable switch modules (asm-16). ? optional network graphic annunciator (nga). ? remote 48 led driver module (anu-48). other component options include a paging microphone and a fire fighter?s handset connecting to the ini-vgc-fo or ini-vgc-utp. each ini-vgc can support up to 16 asm-16 modules. each asm-16 has 16 push-but ton switches for a maximum capacity of 256 switches per ini-vgc command center. each switch has three associated leds, colored green, yellow, and red. these switches and their leds are fully programmable to serve any system function desired.they can control audio speaker ci rcuits, notification appliance circuits, addressable relay outputs, fire fighter phone con- trol circuits, or any other special application that might be required. multiple inccs can be configured into the e3 series broadband network to serve as a completely independent command center to operate for the local area or to operate as remote command centers mimicking, in part or in whole, the function of a main command center. inx (intelligent network transponder) the intelligent network transponder (inx) acts as a network audio transponder for the e3 series broadband network. the inx transponder serves as the point of distri- bution for the system?s audio and fire fighter telephone cir- cuits and occupies a single node on the e3 series broadband network. a typical inx assembly consists of the following compo- nents: ? ili-mb-e3/ili95-mb-e3 ? ili-s-e3/ili95-s-e3 ? anx ? pm-9/pm-9g power supply ? ini-vgx module ? up to four am-50 series amplifiers the inx transponder occupies a single address on the network and provides termination points for the network connection using either a pair of unshielded twisted-pair wire or fiber-optic cable. the inx transponder receives its power from a pm-9/pm- 9g, 9 ampere, filtered, switching power supply providing 24 vdc nominal operating voltage. the pm-9/pm-9g has an integral standby battery charger capable of recharging up to 55 a/h batteries. th e e3bb-bb-bc/inx cabinet can house up to 18 a/h sized batteries. ini-vgx (intelligent network interface-voice gateway) the ini-vgx uses advanced digital signal processing (dsp) technology for audio compression and filtering allowing the e3 series broadband to produce the clearest audio possible while conserving network bandwidth for instantaneous response. background noise is automati- cally filtered during voice paging and fire fighter communi- cations increasing audibility and eliminating the need for push-to-talk devices. the ini-vgx can accommodate up to 16 different mes- sages with a total combined duration of three minutes. each message can be field installed via a laptop computer and can be in the form of a voice message or an evacua- tion tone. the ini-vgx also provides a fire fighter phone riser and an addressable signaling line circuit connecting to multiple phone jacks or warden stations through as many as 16 aom-telf modules. in addition, the ini-vgx slc can support up to 32 speaker circuits using the aom-2sf for single channel applications. am-50 series amplifiers the inx or inx cab-b cabinet can contain up to four am- 50 series amplifiers that produce 50 watts of power @ either 25 v rms or 70.7 v rms audio output. each amplifier includes two separate speaker circuits that can be wired style y (class b) or style z (class a). in addition, each amplifier can produce its own tone or message inde- pendently of other system amplifiers. thus, an inx tran- sponder can produce three audio channels simultaneously. each inx transponder can support up to four am-50 series amplifiers operating as main amplifiers with one am-50 series amplifier used as a fail-safe backup amplifier.
gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 www.gamewell-fci.com 9020-0613 rev. m page 3 of 5 figure 1 incc command center and inx fire fire inx e3 series with 2 notification appliance circuits, each rated 2.0 amps. @ 24 vdc (class 2 power-limited). two analog addressable signaling line circuits (class 2 power-limited) style 7 (class ?a?) incc-c command center with optional microphone and firefighter?s handset asm-16 addressable switch modules with 16 programmable, addressable switches, each with 3 programmable indicating leds: (red, green yellow) inx transponder with 6 independently programmable speaker circuits, each rated 50 watts (class 2 power-limited) three simultaneous audio channels up to 16 programmable voice messages (class 2 power-limited) optional digital alarm communicator transmitter (dact-e3) for local or network- wide event reporting twisted-pair or fiber-optic cable between nodes 3,000 ft. (900m) distance with wire up to 8 db loss with fiber-optic one signaling line circuit with 16-aom-telf and 32 aom-2sf addressable devices (aom-telfs shown) style 4 (class ?b?) standard (class 2 power-limited) firefighter phone riser (class 2 power-limited) fire fire gamewell-fci gamewell-fci
gamewell-fci 12 clintonville road, northford, ct 06472-1610 us a ? tel: (203) 484-7161 ? fax: (203) 484-7118 9020-0613 rev. m page 4 of 5 www.gamewell-fci.com figure 2 e3 series broadband system 3,000 ft. (7,620 cm) (max.) between nodes using wire 8 db loss (max.) between nodes using fiber-optic cable initiating / control devices nac nac fire fire one phone riser one slc (16 aom-telfs & 32 aom-2sfs) 6 speaker appliance ckts. 150 watts max. @ w/ 50 watts standby one phone riser nac nac fire fire local annunciators, lcd-e3 (max. 6) and lcd-7100, (max. 5) global display for all network events if set to region ?0? initiating / control devices one slc (16 aom-telfs & 32 aom-2sfs) one phone riser one slc (16 aom-telfs & 32 aom-2sfs) optional integral dact initiating / control devices local annunciators, lcd-7100, (max. 5) global display for all network events add lcd-e3 (max. 6) fire connect if wired class a, style 6 or 7 only inx inx gamewell-fci inx 6 speaker appliance ckts. 150 watts max. @ w/ 50 watts standby 6 speaker appliance ckts. 150 watts max. @ w/ 50 watts standby e3 series e3 series e3 series gamewell-fci gamewell-fci gamewell-fci gamewell-fci gamewell-fci
gamewell-fci 12 clintonville road, northford, ct 06472-1610 usa ? tel: (203) 484-7161 ? fax: (203) 484-7118 www.gamewell-fci.com 9020-0613 rev. m page 5 of 5 specifications detailed product specificatio ns may be found in the following documents: 9020-0542 incc intelligent network command center data sheet 9020-0637 e3 series control panel data sheet 9020-0541 inx intelligent network transponder data sheet 9021-60758 e3 series combined fire and mass notification data sheet ordering information e3 control part number description ili95-mb-e3 intelligent loop interface-main board ili-mb-e3 intelligent loop interface-main board ili-s-e3 intelligent loop interface-expansion ili95-s-e3 intelligent loop interface-expansion ANX-SR addressable node expander-single ring anx-mr-fo addressable node expander-multi-ring twisted-pair anx-mr-utp addressable node expander-multi-ring fiber-optic lcd-e3 lcd keypad display pm-9/pm-9g power supply rpt-e3 network repeater dact-e3 digital alarm communicator transmitter lcd-7100 (optional) remote serial lcd display incc intelligent network command center part number description ini-vgc command center gateway ini-vgc-utp command center gateway for unshielded twisted-pair wire only asm-16 programmable switch module (occupies single slot of inner door) nga network graphic annunciator anu-48 remote led driver incc-idt inner door w/one double slot for incc-tel fire fighter handset and 4 single slots incc-id inner door w/6 single slots incc-cabr incc backbox (black) with red outer door, dimensions: 19? w x 19? h x 4? d (48 w x 48 h x 10 cm) ordering information (continued) part number description optional accessories anu-48 remote led driver incc-tel fire fighter telephone handset (requires incc-idt inner door) incc-mic paging microphone module (occupies one single slot of inner door) incc-bp command center blank face plate (occupies one single slot of inner door) inx intelligent network transponder ini-vgx transponder voice gateway inx-vgx-utp voice gateway for unshielded, twisted- pair wire only pm-9/pm-9g inx 9 ampere power supply am-50 series amplifiers; am 50-25 inx 50 watt amplifier 25 v rms output am-50-70 inx 50 watt amplifier 70.7 v rms output cabinets: inx-cab inx backbox with black door dimensions; 19? w x 19? h x 4? d (48 x 48 x 10 cm) inx-cabr inx backbox with red door dimensions; 19? w x 19? h x 4? d (48 x 48 x 10 cm) inx cab-b enclosure louvered door and inx-cab-b mounting plate dimensions: 19 3/8? w x 19 3/8? h x 4.5? d (49 w x 39 h x 11 d cm) for additional information on the cabinets, refer to the e3 series cabinets data sheet (part number: 9020-0649). seismic battery bracket kits for information on the types of seismic battery bracket kits available and the seis mic battery bracket kit part numbers, refer to the following documents: ? seismic battery bracket installation guide, p/n: 53839 ? e3 series cabinets data sheet p/n: 9020-0649


▲Up To Search▲   

 
Price & Availability of ANX-SR

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X