 Product data sheet
Sheet No.: 1.604.01 - Rev: E - Page 1 of 3 October, 2006 Date:
FieldQ
Smart - Control Modules
QC01: (24VDC) & QC02: (85-254VAC)
Description:
These FieldQ QC01 and QC02 Smart Control Modules offer an integrated concept for "On/Off" valve automation. Its compact and robust construction incorporates IPT technology with auto-initialization for easy setting of feedback switches. Construction: The Control Module is mounted at the side of the Pneumatic Module in front of the basic actuator housing. Inside are terminals available for connecting control and feedback wiring. Two cable entries are available for this purpose. Features: - Supports both single and double acting actuators. - One entry for all wiring (control and feedback). - IPT-technology (Intelligent Position Tracking). - Automatic initialization for easy setup of the actuator. Pressing 4 seconds simultaneously the "Open" and "Closed" reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches. - Readjustable or Reversible position feedback using the reassignment buttons. - Three indication LED's for "Status", "Open" and "Closed" position. Status LED indicates: - Initialization procedure running (blinking) - Successful initialization procedure (LED is on) - No or failed initialization (flashing) - Control Module is easily plugged in the Pneumatic Module. - Modular functionality for easy update towards present and future bus systems. - The power supply and all inputs and outputs are galvanic isolated which offers greater flexibility for systems connection.
General Specifications:
Material housing Cable entries Electrical connections Enclosure Finish Operating media Temperature Dimensions : : : : : Aluminium alloy 2x M20x1.5 or 2x 1/2"NPT Internal terminal strip. IP65 / NEMA 4X Polyester non-TGIC based powder coating. : Air or inert gasses, filtered at 50 micron : -20 to +80C / -4 to 176F : See 1.603.01 metric See 1.603.04 imperial/UNC See 1.603.02 DIN 3337
FieldQ Button board
Closed reassignment button
Push 4 sec.
Closed LED Status LED Open LED Open reassignment button
Status LED:
on off on off Time LED = Flashing LED = Blinking
TM
www.FieldQ .com Copyright (c) Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center: America's: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.01 - Rev: E - Page 2 of 3 October, 2006 Date:
FieldQ
Smart - Control Modules
QC01: (24VDC) & QC02: (85-254VAC)
Options:
Manual Control - Can be added as kit or factory option in 2 versions, "Push button" or a "Push and lock" button. Glands and plugs - FieldQ Control Modules QC01 or QC02 can be shipped with plastic or metal glands (M20x1.5 or 1/2"NPT) and rated IP65/NEMA4X or higher. Hazardous area modules: - Non-Incendive of Non-Sparking - Control Modules QC01 and QC02 are available with optional Non-Incendive of Non-Sparking approvals as listed below: - ATEX : II 3 GD EEx nA IIC T4 T90C / IP65 : Certificate : KEMA 02ATEX1258X : Ambient temperature: - QC01: -20C...+75C (-4F...167F) - QC02: -20C...+73C (-4F...163F) - FM : Non-Incendive, Class I, II, III, Div.2, Group ABCDFG T4, Type 4X/IP65 : Class I, Zone 2, IIC T4 : Ambient temperature: - QC01: -20C...+75C (-4F...167F) - QC02: -20C...+73C (-4F...163F) - CSA : Non Incendive: Class I, II, III, Div.2, Groups ABCDFG, T4 : Ex nA II T4 (Class I, Zone 2) : Ambient temperature: - QC01: -20C...+75C (-4F...167F) - QC02: -20C...+73C (-4F...163F) : Certificate: 1477696 - Intrinsically safe: - For information about intrinsically safe Control Modules, see 1.604.011 - Short circuit monitoring and line break detection - For information about Control Modules with short circuit monitoring and line break detection (IEC 60947 part 5-6, NAMUR switch characteristics), see 1.604.011
TM
www.FieldQ .com Copyright (c) Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center: America's: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.01 - Rev: E - Page 3 of 3 October, 2006 Date:
FieldQ
Wiring & Electrical Specifications QC01 & QC 02
QC01
Field wiring Unit wiring 1-2 Feedback 2
0-30 VDC/VAC 0.5 Amax. 15VAmax.
3-4 Feedback 1
0-30 VDC/VAC
0.5 Amax. 15VAmax.
5-6 Control supply voltage 7-8 Power supply voltage
24 VDC +/- 15%
24 VDC +/- 15%
+
1 2 3 4 5 6 7 8
QC01, 24VDC electric connections, separate circuits
Field wiring Unit wiring 1-2 Feedback 2,
0.5 Amax. 15VAmax.
3-4 Feedback 1
0.5 Amax. 15VAmax.
5-6 Control
7-8 Power supply voltage
24 VDC +/- 15%
+
1 2 3 4 5 6 7 8
QC01, 24VDC electric connections, common "-"
Electrical data QC01 : 24VDC Power supply input : Voltage 24 VDC (15%) Maximum current 125 mA Power (nominal) 2.5 W Control signal input : Voltage 24 VDC (15%) Maximum current 5 mA Contacts Potential free Feedback switches output: Voltage 0-30 VDC Current DC 500 mA (maximum) 1 mA (advised minimum) Resistance (nom.) 0.5 Ohm (On state) Maximum power 15 W Electric contacts Potential free Polarity: Dependent Power supply Independent Control signal + feedback switches. - For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area applications, see Installation Guide : DOC.IG.QC01.1
QC02
Field wiring Unit wiring 1-2 Power supply voltage 3-4 Control supply voltage
85-254 VAC
85-254 VAC
5-6 Feedback 1
0-254VAC/VDC 150mAmax. 15VAmax.
7-8 Feedback 2
0-254VAC/VDC 150mAmax. 15VAmax.
1N 2L 3 4 5 6 7 8
QC02, 85-254VAC electric connections, separate circuits
Field wiring Unit wiring 1-2 Power supply voltage 3-4 Control supply voltage
85-254 VAC
5-6 Feedback 1
150mAmax. 15VAmax.
7-8 Feedback 2
150mAmax. 15VAmax.
1N 2L 3 4 5 6 7 8
Electrical data QC02 - 85-254VAC Power supply input : Voltage 85-254V (rated mains 95-230V) 50/60Hz Maximum current (* 60 mA Power (nominal) 2.8 W Control signal input : Voltage 85-254V 50/60Hz Maximum current 2.5mA at 115 VAC 5mA at 230 VAC Feedback output: Voltage 0-254 Vac/dc 50/60Hz Maximum current 150mA (AC or DC) Maximum power 15 W Electric contacts Potential free
(*
The QC02 module has a fuse in the supply live line. It is not allowed to replace this fuse in the field. - For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area applications, see Installation Guide : DOC.IG.QC02.1
QC02, 85-254VAC electric connections, single power
TM
www.FieldQ .com Copyright (c) Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center: America's: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)